Test was performed in a pharmaceutical facility on a process 800-ton chiller/ cooling tower system with a 3,000 gallon capacity
Particle Counts Per 100mL Test Portion |
Micron |
Before ELECTROchem
Filter Installation
(07-25-2001) |
After ELECTROchem
Electrostatic Filter
(08-29-2001) |
1 - 3 |
1,309,584 |
159,706 |
3 - 5 |
101,488 |
25,626 |
5 - 10 |
63,808 |
13,422 |
10 - 15 |
11,952 |
2,182 |
15 - 25 |
13,056 |
2,182 |
Over 25 |
22,720 |
1,306 |
Total 100/mL |
1,522,608 |
204,234 |
TEST METHOD: Samples analyzed by electro-optical particle analyzer employing the light scattering principle of operation in a dilute ratio 1:15 with filtered water and particle data corrected |
Solids Per 100 Liters of System Volume (mm3) |
Micron |
Before ELECTROchem
Filter Installation
(07-25-2001) |
After ELECTROchem
Electrostatic Filter
(08-29-2001) |
1 - 5 |
17 |
3 |
5 - 10 |
27 |
6 |
Over 10 |
15,327 |
893 |
Total 100/Liters |
15,371 154ppm |
901 9ppm |
TEST METHOD: Samples analyzed by electro-optical particle analyzer employing the light scattering principle of operation in a dilute ratio 1:1 with filtered water and particle data corrected
Note: Typical sand filter size for this operation would use 300 gallon per backwash ELECTROchem filter backwash water used - 0 |
|
Specifications / Physical Description (Typical 1000-ton Tower) |
Dimensions: |
Weight 400 lbs (181.4kg)
Height 48" (121.92cm)
Footprint 32" x 35" Skid Mount (81.28cm x 91.44cm) |
Operating PSI: |
15-30 psi |
Electrical: |
120-240V AC Single Phase 60/50 Hz
12/6 Amps
1hp Pump |
Piping: |
Inlet 2" (5.08cm) (15-80 gpm adjustable)
Outlet 2" (5.08cm)